Moeller Products


EASY Relay

Easy Overview
Easy expansion
Easy Applications
Easy 400
Easy 600
Easy 800
MFD Titan
Technical Data
 
 

Technical Data Overview






 
 
The following applies for all 'easy' units:
Connection cables
0.2 – 0.25 mm², flexible/ 0.2 – 4.0 mm², solid
Degree of protection IP 20
Interference suppression EN 55 011/55 022 class B
Operating
temperature
-25°C to +55°C
Transport and storage temperature -40°C to + 70°C
Certification, standard EN 50 178, IEC/EN 60947, UL, CSA
Fitting On a top-hat rail to DIN 50 022, 35 mm or
screw fixing with ZB4-101-GF1 fixing bracket.
 

 






 
 
Expansions
Digital inputs/outputs
Expansions
Communication
EASY...
618-
AC-
RE
618-
DC-
RE
620-
DC-
TE
202-
RE
200-
EASY
204-
DP
205-ASI
221-
CO
222-
DN
Supply
voltage
115/240 V AC
24 V DC
24 V DC
24 V DC
24 V DC
Power dissipation
 
 
10 VA
4 W
1 W
 
 
1 W
2 W
1 W
2 W
2 W
Inputs,
digital
12
12
12
Inputs,
analog,
option (0-10 V)
2
2
2
2
2
2
Outputs,
digital (R=relay
T=transistor)
 
6 R
6 R
8 T
2 R
Outputs,
analog,
(0-10 V)
LC display,
keypad
Week/
Year clock
–/–
–/–
–/–
–/–
–/–
–/–
–/–
–/–
–/–
Output
continuous current
8 A
8 A
0.5 A
8 A
Short-circuit proof
at cos phi = 1
Line protection
B 16, 600 A
B 16,
600 A
Short-circuit proof
at cos phi=
0.5...0.7
Line protection
B 16, 900 A
B 16,
900 A
Dimensions in mm
(W x H x D)
 
107.5 x 90 x 58 mm
35.5 x 90 x 58 mm
 

 






 
 

Switching mode power supplies

 
EASY ...
200-POW
400-POW
Input voltage range
85 to 264 V AC
85 to 264 V AC
Output voltage
24 V DC +/- 3%
24 V DC +/- 3%
Output current, nominal value
0.25 A
1.25 A
Overcurrent limitation
from 0.3 A
from 1.4 A
General
Auxiliary output voltage 12 V DC, 20 m A for analog supply
Potential isolation,
primary/secondary
Yes, SELV
(to EN 60 0950, VDE 805)
Yes, SELV
(to EN 60 0950, VDE 805)
Short-circuit proof (secondary)
Yes
Yes
Overload protection (secondary)
Yes
Yes
Dimensions in mm
(W x H x D)
35.5 x 90 x 58 mm
71.5 x 90 x 58 mm