The ‘easy’ 400 Control Relay
|
Eight inputs, four relay or transistor outputs.
In all the DC variants, there is the option of two analog inputs.
The easy412 has three contacts and one coil for circuit
configuration in each of up to 41 lines of logic.
Features |
-
8 inputs
-
4 relay or outputs
-
4 line LCD display
-
Program in Ladder Diagram
-
Up to 41 lines of logic
-
No programming software required
-
Analog inputs (DC devices)
-
Real time clock (C devices)
-
Dynamic "Power Flow" Display
-
Password protection function
-
120/240 V AC and 24 V DC models
-
Easy 412-DC stores up to 4 markers plus
actual values of a timing relay and a counter
-
Choice of 5 languages for menu display
-
Operates easily at -13°F to 131°F
|
|
|
|
|
|
400 series
basic units
|
EASY... |
412-
AC-
R
|
412-
AC-
RC
|
412-
AC-
RCX
|
412-
DC-
R
|
412-
DC-
RC
|
412-
DC-
RCX
|
412-
DC-
TC
|
412-
DC-
TCX
|
412-
DA-
RC
|
Supply
voltage |
115/240
V AC
|
24 V DC
|
12 V DC |
Power
dissipation |
5 VA
|
2 W
|
Inputs,
digital |
8
|
8
|
8
|
8
|
8
|
8
|
8
|
8
|
8
|
Inputs,
analog,
option (0–10 V) |
–
|
–
|
–
|
2
|
2
|
2
|
2
|
2
|
2
|
Outputs,
digital (R=relay
T=transistor)
|
4 R
|
4 R
|
4 R
|
4 R
|
4 R
|
4 R
|
4 T
|
4 T
|
4 R
|
Outputs,
analog,
(0–10 V) |
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
–
|
LC
display,
keypad |
Yes
|
Yes
|
–
|
Yes
|
Yes
|
–
|
Yes
|
–
|
Yes
|
Week/
Year clock |
–/–
|
Yes/–
|
Yes/–
|
–/–
|
Yes/–
|
Yes/–
|
Yes/–
|
Yes/–
|
Yes/–
|
Output
continuous current |
8 A
|
8 A
|
8 A
|
8 A
|
8 A
|
8 A
|
0.5 A
|
0.5 A
|
8 A
|
Short-circuit proof
at cos phi = 1 |
Line protection B 16, 600 A
|
–
|
–
|
B 16,
600 A
|
Short-circuit proof
at cos phi =
0.5...0.7 |
Line protection B 16, 900 A
|
–
|
–
|
B 16,
900 A
|
Dimensions in mm
(W x H x D) |
71.5 x
90 x 58 mm
|
|
|
|
|
|
|
|