Sola Hevi-Duty Products
S D N - P |
ADDITIONAL FEATURES & SPECIFICATIONS |
How did the best power supply get better?
|
Specifications: |
Description |
Catalog Number |
||||
SDN 2.5-24-100P |
SDN 4-24-100P | SDN 5-24-100P | SDN 10-24-100P | SDN 20-24-100P | |
Input |
|||||
Nominal Voltage |
115/230 VAC user select (no manual required) |
||||
-AC Range |
85-132/176-264 VAC |
||||
-DC Range |
90-375 VDC |
210 - 375 VDC |
N/A |
||
-Frequency |
47 - 63 Hz, 400 Hz Possible |
||||
Nominal Current1 |
1.3 A. / 0.7 A |
2.6 A. / 1.4 A | 6 A / 2.8 A typical | 12 A/6 A | |
-Inrush current max. |
typ. <25 A | typ. <20 A | typ. <40 A | ||
Efficiency (Losses2) |
>87.5% typ |
>88% typ (13.1 W) |
>88% typ (16.4 W) | >88% typ (32.7 W) |
>90% typ (48 W) |
Output |
|||||
Nominal Voltage |
24 VDC (22.5 - 28.5 VDC Adj.) |
||||
-Tolerance |
<±2% overall (combination line, load, time and temperature related changes) |
||||
-Ripple3 |
< 50 mVpp |
||||
Nominal Current |
2.5 A (60 W) |
4 A (100 W) |
5 A (120 W) |
10 A (240 W) |
20 A (480 W) |
-Peak Power4 |
2x Nominal Current |
4.2 A max |
6 A |
12 A |
2x Nominal Current |
-Current Limit |
Fold Forward
(Current rises, voltage drops to maintain constant power during overload up to max peak current) |
||||
Holdup Time |
> 20 ms (Full load, 100 VAC Input @ Tamb = +25oC to 95% output voltage. |
||||
Parallel Operation | Single or Parallel use is selectable via Front Panel Jumper. | ||||
General |
|||||
EMI -Emissions |
EN50081-1,-2 Class B EN55011, EN55022 Radiated and Conducted including Annex A. | ||||
-Immunity | EN50082-1, -2; EN61000-4-2
Level 4, EN61000-4-3 Level 3; EN61000-4-6 Level 3; EN61000-4-4 Level 4 input and Level 3 output; EN61000-4-5 Isolation Class 4 (SDN8-5-24 is Class 3), EN61000-4-11; Transient resistance according to VDE 0160/W2 over entire load range. |
||||
Approvals | EN60950; EN50178; EN60204;
UL508 Listed, cULus; UL1950, cRUus, SDN4 & 2.5 - Class 2 LPS; CE (LVD 73/23 & 93/68/EWG, EMC 89/336 & 93/68/EWG; Transient Handling VDE 0160/W2. SDN 8-5-24 is CE marked with SE>V<42 V only. |
||||
Temperature | Storage: -25oC...+85oC
Operation. -10o-60oC full power with operation to 70oC
possible with a linear derating to half power from 60oC to 70oC. The relative humidity is 95% maximum non condensing. |
||||
Warranty |
5 years |
||||
General Protections/ Safety |
Protected against
short-circuit, overload, open-circuit. Overvoltage protection (OVP) for
output set @32 V ±10%. Protection class I (IEC536), degree of protection: IP20 (VDE 0470, IEC 529) Safe low voltage: SELV (acc. EN60950). |
||||
Status Indicators |
Green LED and DC OK signal (300 mA @ 60 VDC) | ||||
Installation |
|||||
Fusing | |||||
-Input | Internally fused. External
10 A slow acting fusing for the input is recommended for SDN2.5, 4 5 and 10P models. A 16A slow acting fuse or time-delay circuit breaker is recommended for the SDN20 model. |
||||
-Output | Outputs are capable of
providing high currents for short periods of time for inductive load startup
or switching. Fusing may be required for wire/loads if 2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping. |
||||
Mounting | Simple snap-on system for
DIN Rail TS35/7.5 or TS35/15 or chassis-mounted (optional screw mounting set SDN-PMBRK2 required). |
||||
Connections | Input:
IP20-rated screw terminals, connector size range: 16-10 AWG (1.5-6 mm2)
for solid conductors. 16-12 AWG (0.5-4 mm2) for flexible conductors. Output: Two connectors per output, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors. |
||||
Case | Fully enclosed metal housing with fine ventilation grid to keep out small parts. | ||||
-Free Space |
25 mm above/below |
25 mm above/below |
70 mm above/below |
||
H x W x D (inches/mm) |
4.88 x 1.97 x 4.55 |
4.88 x 2.56 x 4.55 |
4.88 x 3.26 x 4.55 |
4.88 x 6.88 x 4.55 |
|
Weight (lbs/g) |
1 lb (460g) |
1.5 lb (620g) |
2.2 lbs (1100g) | 3 lbs (1520g) | |
Notes: |
Description |
Catalog Number |
||||
SDN 5-24-480 |
SDN 10-24-480 |
SDN 20-24-480C | SDN 30-24-480 | SDN 40-24-480 | |
Input |
|||||
Nominal Voltage |
3Æ 380-480 |
1Æ or 3Æ, 380 - 480 VAC1 |
3Æ 380-480 VAC | ||
-AC Range |
340-576 VAC |
||||
-DC Range | 450 - 820 VDC | ||||
-Frequency |
47 - 65 Hz |
||||
Nominal Current2 | 0.5 A | 1 A | 1.5 A | 2.0 A | 3.0 A |
-Inrush current | typ. < 18 A | typ. < 30 A | |||
Efficiency (Losses2) |
>90% typ (12 W) | >90% typ (48 W) | >90% typ (72 W) | >90% typ (96 W) | |
Power Factor Correction |
Units fulfill EN61000-3-2 |
||||
Output |
|||||
Nominal Voltage |
24-28 VDC Adj. (22.3 - 28.5 VDC adj.) |
||||
-Tolerance |
<±2% overall (combination line. load, time and temperature related changes) |
||||
-Ripple4 | < 50 mVpp | ||||
Nominal Current |
5 A (120 W) |
10 A (240 W) |
20 A (480 W) |
30 A (720 W) |
40 A (960 W) |
-Peak Current |
6 A |
12 A |
25 A |
35 A |
45 A |
-Current Limit |
Fold Forward |
||||
Holdup Time |
>20 ms |
||||
Parallel Operation |
The SDN20/30 may be
passively paralleled by selecting the "P" position of the jumper on the
unit. The SDN40 contains active current balancing. |
||||
General |
|||||
EMI -Emissions |
EN50081-1,-2 Class B EN55011, EN55022 Radiated and Conducted including Annex A. | ||||
EMI -Immunity |
EN50082-1, -2; EN61000-4-2
Level 4, EN61000-4-3 Level 3; EN61000-4-6 Level 3; EN61000-4-4 Level 4 input and Level 3 output; EN61000-4-5 Isolation Class 4, EN61000-4-11; Transient resistance according to VDE 0160/W2 over entire load range. |
||||
Approvals | CB Scheme, EN60950;
EN50178; EN60204; UL508 Listed, cULus; UL60950, cRUus, CE (LVD 73/23 & 93/68/EEC). EN61000-3-2, IEC 60079-15 (Class 1, Zone 2 hazardous location, Groups IIA, IIB, IIC w/T3 temp class up to 60°C Ambient. |
||||
Temperature | Storage: -25oC...+85oC
Operation. -10o-60oC full power with operation to 70oC
possible with a linear derating to half power from 60oC to 70oC. (Convection cooling, no forced air required). Operation up to 50% load permissable with sideways or front side up mounting orientation. The relative humidity is less <90% RH, noncondensing; IEC 68-2-2, 68-2-3. |
||||
Warranty |
5 years |
||||
General Protection/ Safety |
Protected against
continuous short-circuit, overload, open-circuit. Protection class 1
(IEC536), degree of protection IP20 (IEC529). Safe low voltage: SELV (acc. EN60950). |
||||
Status Indicators | Green LED on, when Vout = 18V or greater. | ||||
Installation |
|||||
Fusing | |||||
-Input | Internally fused. | ||||
-Output | Outputs are capable of
providing high currents for short periods of time for inductive load startup
or switching. Fusing may be required for wire/loads if 2x Nominal O/P current rating cannot be tolerated. Continuous current overload allows for reliable fuse tripping. |
||||
Mounting | Simple snap-on system for
DIN Rail TS35/7.5 or TS35/15 or chassis-mounted (optional screw mounting set SDN-PMBRK2 required). |
||||
Connections | Input:
IP20 related screw terminals, connector size range: 16-10 AWG (1.5-6 mm2)
for solid conductors. 16-12 AWG (0.5-4 mm2) for flexible conductors. Output: two connectors per output, connector size range: 16-10 AWG (1.5 - 6 mm2) for solid connectors. |
||||
Case | Fully enclosed metal housing with fine ventilation grid to keep out small parts. | ||||
-Free Space |
25 mm above/below |
70 mm above/below |
|||
H x W x D (inches/mm) |
4.88 x 2.91 x 4.55 |
4.88 x 3.5 x 4.55 |
4.88 x 5.9 x 4.55 |
4.88 x 9.72 x 4.55 |
4.88 x 11.1 x 4.55 |
Weight (lbs/g) |
1.7 lbs (730g) |
2.16 lbs (980g) |
3.97 lbs (1800g) |
4 lbs (2000g) | 6.6 lbs (3300g) |
Notes: |
Contact us for additional information about the SDN-P.