SpikeShield TDR Series
The
SpikeShield family of power quality products from Hubbell has been
expanded to include the new TDR offering of noise filtration and
surge protection products. The TDR products are a family of
series-wired products that feature a 40KA peak amp surge rating and
up to -75dB of noise filtration. Load ratings of 5 Amps, 15 Amps and
20 Amps are now available in the 120-Volt model and all may be
ordered with or without a set of dry contacts for remote signaling
capability. The 220-Volt model is available in a 20 Amp version and
comes standard with dry contacts. All TDR models come with an
integral DIN rail mounting system and a set of attachable mounting
feet that allows the device to be flange mounted.
|
Product
Specifications |
Product Type |
DIN Rail Mount
|
Peak Current Rating |
40KA
|
Voltage |
120V AC
|
Mounting Style |
DIN RAIL
|
Amperage |
5 Amps
|
Options |
Without Relay Contacts
|
Dimension H |
5.58" (141)
|
Dimension W |
4.00" (101)
|
Dimension D |
2.23" (57)
|
Surge LED |
Green Status LED
|
UL Clamping Voltage |
330V AC
|
LED Color |
Green
|
Frequency |
50/60/400 Hz
|
Maximum Surge Current per
Phase |
40 KA per phase
|
Maximum surge current per
mode |
20 KA L-N, L-G, N-G
|
Product Warranty |
Product- 10 Years
|
Dry Contacts |
Form C, Dry
|
Normal EMI/RFI Rejection (@ 50
Ohms) |
Up to -75 dB
|
Terminal Accommodation |
Screw Terminals/ #12 AWG CU
|
Thermal Fusing |
Yes
|
ANSI/IEEE C62.41 Clamping
Voltage:Category A3 200A(Ringwave) |
180V/380V
|
ANSI/IEEE C62.41 Clamping
Voltage:Category B3 500A(Ringwave) |
185V/390V
|
ANSI/IEEE C62.41 Clamping
Voltage:Category C1 3000A(Impulse) |
300V/740V
|
Housing Rating |
NEMA 1
|
Product Weight Pounds |
1 Pound
|
Max Load Rating |
5 Amp
|
Operating Temperatures |
-40 Deg F to 140 Deg F (-40Deg
C to 70 Deg. C) |
Features/Benefits |
Series/Hybrid Design.
-75dB noise Filtration.
UL 1449 & 1283.
Optional Dry Contacts.
5A, 15A & 20A Versions.
330 Volt UL Clamping Level.
CE Mark.
10 Year Warranty. | |